🤖 AI Summary
本文通过扩展GridFM模型,嵌入下垂增益和死区参数,并使用基于变压器的图神经网络解决不同控制机制下的交流潮流分析问题。
📝 Abstract
This paper develops a droop-aware extension of the GridFM power systems foundation model, embedding droop gains and frequency/voltage deadband parameters as per-bus node features to enable control-aware AC power-flow analysis. Existing power-flow datasets encode only static electrical features, conflating operating points from qualitatively different control regimes; this work resolves that gap by exposing droop and deadband parameters as structured node features, with deadband discontinuities handled through a smooth tanh approximation that preserves solver differentiability. A transformer-based graph neural network is pre-trained on masked reconstruction and fine-tuned on the resulting control-aware datasets. The framework is validated against PSCAD electromagnetic-transient simulations on a two-bus system (0.11% maximum steady-state error) and cross-validated against an independent PyPower droop solver on the IEEE 24-bus RTS. On the 24-bus system the surrogate attains R2 = 0.9996 for active generation and 0.0015 p.u. voltage-magnitude RMSE; scalability is confirmed on the IEEE 300-bus system (0.0036 p.u. RMSE, R2 = 0.9841 for voltage magnitude across 299,700 predictions). A three-mode control study further shows that the deadband widens the control-error distribution while leaving total droop compensation unchanged, establishing deadband width as an actionable node-level design feature.